浙大中控DCS卡件日常維護時需要對哪些數據進行備份?

2021-01-18 18:28:52 來源:http://www.qistar-garment.net/ 53

浙大中控DCS卡件日常維護時需要對哪些數據進行備份?
What data should be backed up during daily maintenance of DCS card in Zhejiang University?
需要對組態、PID參數、工藝參數(設定值)、係統安裝軟件、電腦驅動以及認為重要的趨勢、報表等數據進行備份。
It is necessary to back up the configuration, PID parameters, process parameters (set values), system installation software, computer drivers, trends and reports that are considered important.
回路無輸出問題的處理?
How to deal with the problem of no output in the loop?
某項目使用中控JX-300X係統。用戶自行增加一單回路後,無輸出。投自動時會自動跳回手動狀態。經檢查程序,發現用戶增加的自定義回路,回路編號為09;而BSC模塊中,模擬量輸出對應的模塊為08。而08自定義回路組態後前期並未實際應用。因此用戶在回路程序段中發現前期使用的回路號為07,便自行將08回路號將在本次增加的BSC模塊內。因此,在組態下載後,回路與實際輸出並未一一對應,因此發生本次故障。將程序中BCS模塊的回路編號更改為09,編譯下載後正常。
A project uses central control JX-300X system. After the user adds a single circuit, there is no output. It will automatically jump back to the manual state when it is automatic. After checking the program, it is found that the user-defined circuit number is 09, while the module corresponding to analog output in BSC module is 08. However, 08 custom loop configuration has not been applied in practice. Therefore, if the user finds that the previously used loop number is 07 in the loop program section, he will put the 08 loop number in the BSC module added this time. Therefore, after the configuration download, the circuit and the actual output did not correspond one by one, so this fault occurred. The circuit number of BCS module in the program is changed to 09, which is normal after compiling and downloading.
主控卡故障排除案例:
Troubleshooting case of main control card:
故障現象:某JX-300X DCS卡件係統檢修後發現兩塊主控卡都不工作,主控卡所有的指示燈都不亮。
Fault phenomenon: after maintenance of a JX-300X DCS card system, it is found that two main control cards are not working, and all indicator lights of the main control card are not on.
             浙大中控DCS卡件
故障排除:
Troubleshooting:
1.將兩塊主控卡依次重新插在相鄰控製站主控卡位置,主控卡指示燈正常顯示,排除主控卡本身硬件故障。
1. Insert the two main control cards into the main control cards of the adjacent control station in turn, and the indicator light of the main control card will display normally, so as to eliminate the hardware fault of the main control card.
2.將一塊IO卡件插在原主控卡槽位,IO卡件指示燈顯示正常,基本將故障點定在主控卡槽位上。3.萬用表測量各機籠後5V、24V電壓:主控卡機
2. Insert an IO card into the original master card slot, the indicator light of IO card is normal, and the fault point is basically located in the master card slot. 3. Measure the 5V and 24V voltage behind each cage with a multimeter: main control card
籠和二個機籠24V為0;測量電源箱後電源5V、24V供電都正常,而24V輸出到機籠的接線斷開,重新接上24V電源線後,主控卡正常工作,故障消除。
The 24 V of the cage and the two cages is 0; after measuring the power supply box, the power supply of 5 V and 24 V is normal, and the wiring of 24 V output to the cage is disconnected. After re connecting the 24 V power line, the main control card works normally and the fault is eliminated.
以上是"浙大中控DCS卡件日常維護時需要對哪些數據進行備份"介紹,希望對大家有所幫助,如想了解更多精彩資訊請點擊丝瓜视频免费草莓视频免费下载的網站:http://www.qistar-garment.net
The above is the introduction of "what data need to be backed up during daily maintenance of DCS card of Zhejiang University central control". I hope it can help you. For more wonderful information, please click our website: http://www.qistar-garment.net  .